CC, linear CC, CR, CV, CP and AC rectifier load reproduce linear and non-linear loading.
AEL-5000 – Programmable Electronic AC/DC Load up to 22.5 kW
For load and protection testing of UPS systems, inverters and power supplies with programmable current waveforms.
The AEL-5000 series comprises programmable AC/DC electronic loads rated from 1,875 to 22,500 W for voltages up to 480 Vrms or 700 Vdc. A time-limited Turbo mode doubles model-dependent RMS current and power for short-circuit, fuse, OCP and OPP tests.
Crest factor, power factor, load angles, half-wave loading and SCR/TRIAC phase control are configurable.
Voltage, current, real and apparent power, frequency, PF, CF, plus voltage and current harmonics are measured.
Up to eight identical units operate in a master-slave system; three-phase Δ and Y configurations are supported.
Personal project consultation
Do you need support selecting the right power supply? Our technical specialists will provide personal advice tailored to your application.
Select the appropriate technical configuration or access product documentation directly.
|
Description
AEL-5002-350-18.75 AC/DC electronic load, 1.875 kW, AC 50–350 Vrms / DC 500 Vdc, 18.75 Arms / 56.25 Apeak, Turbo mode up to 3.75 kW / 37.5 Arms
|
Current [A]
18,75
|
Power [P]
1875
|
Voltage [V]
350
|
Technical Data
Product category
AC Electronic Load
Type of AC Load
Conventional Load
|
Description
AEL-5003-350-28 AC/DC electronic load, 2.8 kW, AC 50–350 Vrms / DC 500 Vdc, 28 Arms / 84 Apeak, Turbo mode up to 5.6 kW / 56 Arms
|
Current [A]
28
|
Power [P]
2800
|
Voltage [V]
350
|
Technical Data
Product category
AC Electronic Load
Type of AC Load
Conventional Load
|
Description
AEL-5004-350-37.5 AC/DC electronic load, 3.75 kW, AC 50–350 Vrms / DC 500 Vdc, 37.5 Arms / 112.5 Apeak, Turbo mode up to 7.5 kW / 75 Arms
|
Current [A]
37.5
|
Power [P]
3750
|
Voltage [V]
350
|
Technical Data
Product category
AC Electronic Load
Type of AC Load
Conventional Load
|
Description
AEL-5002-425-18.75 AC/DC electronic load, 1.875 kW, AC 50-425 Vrms / DC 600 VDC, 18.75 Arms / 56.25 Apeak, turbo mode up to 3.75 kW / 37.5 Arms
|
Current [A]
18,75
|
Power [P]
1875
|
Voltage [V]
425
|
Technical Data
Product category
AC Electronic Load
Type of AC Load
Conventional Load
|
Description
AEL-5003-425-28 AC/DC electronic load, 2.8 kW, AC 50–425 Vrms / DC 600 Vdc, 28 Arms / 84 Apeak, Turbo mode up to 5.6 kW / 56 Arms
|
Current [A]
28
|
Power [P]
2800
|
Voltage [V]
425
|
Technical Data
Product category
AC Electronic Load
Type of AC Load
Conventional Load
|
Description
AEL-5004-425-37.5 AC/DC electronic load, 3.75 kW, AC 50–425 Vrms / DC 600 Vdc, 37.5 Arms / 112.5 Apeak, Turbo mode up to 7.5 kW / 75 Arms
|
Current [A]
37.5
|
Power [P]
3750
|
Voltage [V]
425
|
Technical Data
Product category
AC Electronic Load
Type of AC Load
Conventional Load
|
Description
AEL-5006-350-56 AC/DC electronic load, 5.6 kW, AC 50-350 Vrms / DC 500 VDC, 56 Arms / 168 Apeak, turbo mode up to 11.2 kW / 112 Arms
|
Current [A]
56
|
Power [P]
5600
|
Voltage [V]
350
|
Technical Data
Product category
AC Electronic Load
Type of AC Load
Conventional Load
|
Description
AEL-5008-350-75 AC/DC electronic load, 7.5 kW, AC 50–350 Vrms / DC 500 Vdc, 75 Arms / 225 Apeak, Turbo mode up to 15 kW / 150 Arms
|
Current [A]
75
|
Power [P]
7500
|
Voltage [V]
350
|
Technical Data
Product category
AC Electronic Load
Type of AC Load
Conventional Load
|
Description
AEL-5012-350-112.5 AC/DC electronic load, 11.25 kW, AC 50–350 Vrms / DC 500 Vdc, 112.5 Arms / 337.5 Apeak, Turbo mode up to 22.5 kW / 225 Arms
|
Current [A]
112.5
|
Power [P]
11250
|
Voltage [V]
350
|
Technical Data
Product category
AC Electronic Load
Type of AC Load
Conventional Load
|
Description
AEL-5015-350-112.5 AC/DC electronic load, 15 kW, AC 50–350 Vrms / DC 500 Vdc, 112.5 Arms / 337.5 Apeak, Turbo mode up to 30 kW / 225 Arms
|
Current [A]
112.5
|
Power [P]
15000
|
Voltage [V]
350
|
Technical Data
Product category
AC Electronic Load
Type of AC Load
Conventional Load
|
Description
AEL-5019-350-112.5 AC/DC electronic load, 18.75 kW, AC 50–350 Vrms / DC 500 Vdc, 112.5 Arms / 337.5 Apeak, Turbo mode up to 37.5 kW / 225 Arms
|
Current [A]
112.5
|
Power [P]
18750
|
Voltage [V]
350
|
Technical Data
Product category
AC Electronic Load
Type of AC Load
Conventional Load
|
Description
AEL-5023-350-112.5 AC/DC electronic load, 22.5 kW, AC 50–350 Vrms / DC 500 Vdc, 112.5 Arms / 337.5 Apeak, Turbo mode up to 45 kW / 225 Arms
|
Current [A]
112.5
|
Power [P]
22500
|
Voltage [V]
350
|
Technical Data
Product category
AC Electronic Load
Type of AC Load
Conventional Load
|
Description
AEL-5006-350-56 AC/DC electronic load, 5.6 kW, AC 50–350 Vrms / DC 500 Vdc, 56 Arms / 168 Apeak, Turbo mode up to 11.2 kW / 112 Arms
|
Current [A]
56
|
Power [P]
5600
|
Voltage [V]
425
|
Technical Data
Product category
AC Electronic Load
Type of AC Load
Conventional Load
|
Description
AEL-5008-425-75 AC/DC electronic load, 7.5 kW, AC 50–425 Vrms / DC 600 Vdc, 75 Arms / 225 Apeak, Turbo mode up to 15 kW / 150 Arms
|
Current [A]
75
|
Power [P]
7500
|
Voltage [V]
425
|
Technical Data
Product category
AC Electronic Load
Type of AC Load
Conventional Load
|
Description
AEL-5012-425-112.5 AC/DC electronic load, 11.25 kW, AC 50–425 Vrms / DC 600 Vdc, 112.5 Arms / 337.5 Apeak, Turbo mode up to 22.5 kW / 225 Arms
|
Current [A]
112.5
|
Power [P]
11250
|
Voltage [V]
425
|
Technical Data
Product category
AC Electronic Load
Type of AC Load
Conventional Load
|
Description
AEL-5015-425-112.5 AC/DC electronic load, 15 kW, AC 50–425 Vrms / DC 600 Vdc, 112.5 Arms / 337.5 Apeak, Turbo mode up to 30 kW / 225 Arms
|
Current [A]
112.5
|
Power [P]
15000
|
Voltage [V]
425
|
Technical Data
Product category
AC Electronic Load
Type of AC Load
Conventional Load
|
Description
AEL-5019-425-112.5 AC/DC electronic load, 18.75 kW, AC 50–425 Vrms / DC 600 Vdc, 112.5 Arms / 337.5 Apeak, Turbo mode up to 37.5 kW / 225 Arms
|
Current [A]
112.5
|
Power [P]
18750
|
Voltage [V]
425
|
Technical Data
Product category
AC Electronic Load
Type of AC Load
Conventional Load
|
Description
AEL-5002-425-18.75 AC/DC electronic load, 1.875 kW, AC 50–425 Vrms / DC 600 Vdc, 18.75 Arms / 56.25 Apeak, Turbo mode up to 3.75 kW / 37.5 Arms
|
Current [A]
112.5
|
Power [P]
22500
|
Voltage [V]
425
|
Technical Data
Product category
AC Electronic Load
Type of AC Load
Conventional Load
|
Description
AEL-5003-480-18.75 AC/DC electronic load, 2.8 kW, AC 50–480 Vrms / DC 700 Vdc, 18.75 Arms / 56.25 Apeak, Turbo mode up to 5.6 kW / 37.5 Arms
|
Current [A]
18,75
|
Power [P]
2800
|
Voltage [V]
480
|
Technical Data
Product category
AC Electronic Load
Type of AC Load
Conventional Load
|
Description
AEL-5004-480-28 AC/DC electronic load, 3.75 kW, AC 50–480 Vrms / DC 700 Vdc, 28 Arms / 84 Apeak, Turbo mode up to 7.5 kW / 56 Arms
|
Current [A]
28
|
Power [P]
3750
|
Voltage [V]
480
|
Technical Data
Product category
AC Electronic Load
Type of AC Load
Conventional Load
AEL-5000 series overview
The AEL-5000 is a series of programmable AC/DC electronic loads for testing AC and DC sources. The model range covers rated power from 1,875 to 22,500 W, 18.75 to 112.5 Arms and up to 337.5 Apeak. Three voltage families cover 50 to 350, 425 or 480 Vrms and up to 500, 600 or 700 Vdc. In addition to CC, CR, CV and CP, the series supports linear CC and non-linear rectifier load operation for AC applications. Programmable current waveforms, load and unload angles, half-wave operation, crest factor and power factor reproduce typical loads for UPS systems, inverters and power supplies. A time-limited Turbo mode increases RMS current and power to twice the rating for protection-component and limit tests. Measurement, test, storage and sequence functions, plus optional GPIB, RS-232, USB or LAN interfaces, support automated test systems.
Key benefits
Twice the load for short tests
For fuse, short-circuit, OCP and OPP tests, Turbo doubles rated current and power within defined time limits.
One load for two signal types
AC and DC operation plus CC, linear CC, CR, CV, CP and rectifier load cover different sources and load characteristics.
Reproduce real current waveforms
Adjustable CF and PF, 0–359° load angles, half-wave loading and SCR/TRIAC current waveforms support non-linear load testing.
Measure electrical quantities directly
The 16-bit measurement circuit captures RMS, peak, maximum and minimum values plus power, frequency, CF, PF, THD and harmonics.
Built-in test routines
Predefined functions support UPS, battery, fuse, short-circuit, OCP, OPP and inrush-current testing, among other tasks.
Scale single- and three-phase tests
Identical units can operate in a master-slave system and combine into synchronised three-phase Δ or Y loads.
How the AC/DC electronic load operates
The AEL-5000 absorbs electrical power from the connected device under test. In constant-current operation, CC regulates the current to the programmed setpoint. Linear CC transfers the shape of the input voltage to the load current, making it suitable for step, square and PWM voltage sources. In CR mode, current rises in proportion to voltage, while CP keeps absorbed power constant. In CV mode, the load sinks enough current to reach the programmed input voltage.
For AC tests, non-linear rectifier load operation supplements these control modes. Crest factor and leading or lagging power factor shape the load current. Load and unload angles, positive or negative half-wave loading and 90° SCR/TRIAC waveforms enable defined asymmetric and phase-controlled loads. In AC and DC setups, voltage, RMS current, peak current and power must simultaneously remain within the selected model's operating envelope.
Models, power ratings and voltage families
Rated values apply to each individual unit with Turbo disabled. Within the permitted test duration, Turbo doubles RMS current and power; the specified peak current remains unchanged. Turbo operation is intended for the Fuse, Short, OCP and OPP test functions.
| Model | Voltage range | Rated / Turbo power | Rated / Turbo current | Peak current |
|---|---|---|---|---|
| AEL-5002-350-18.75 | 50–350 Vrms / 500 Vdc | 1,875 / 3,750 W | 18.75 / 37.5 Arms | 56.25 Apeak |
| AEL-5003-350-28 | 50–350 Vrms / 500 Vdc | 2,800 / 5,600 W | 28 / 56 Arms | 84 Apeak |
| AEL-5004-350-37.5 | 50–350 Vrms / 500 Vdc | 3,750 / 7,500 W | 37.5 / 75 Arms | 112.5 Apeak |
| AEL-5002-425-18.75 | 50–425 Vrms / 600 Vdc | 1,875 / 3,750 W | 18.75 / 37.5 Arms | 56.25 Apeak |
| AEL-5003-425-28 | 50–425 Vrms / 600 Vdc | 2,800 / 5,600 W | 28 / 56 Arms | 84 Apeak |
| AEL-5004-425-37.5 | 50–425 Vrms / 600 Vdc | 3,750 / 7,500 W | 37.5 / 75 Arms | 112.5 Apeak |
| AEL-5006-350-56 | 50–350 Vrms / 500 Vdc | 5,600 / 11,200 W | 56 / 112 Arms | 168 Apeak |
| AEL-5008-350-75 | 50–350 Vrms / 500 Vdc | 7,500 / 15,000 W | 75 / 150 Arms | 225 Apeak |
| AEL-5012-350-112.5 | 50–350 Vrms / 500 Vdc | 11,250 / 22,500 W | 112.5 / 225 Arms | 337.5 Apeak |
| AEL-5015-350-112.5 | 50–350 Vrms / 500 Vdc | 15,000 / 30,000 W | 112.5 / 225 Arms | 337.5 Apeak |
| AEL-5019-350-112.5 | 50–350 Vrms / 500 Vdc | 18,750 / 37,500 W | 112.5 / 225 Arms | 337.5 Apeak |
| AEL-5023-350-112.5 | 50–350 Vrms / 500 Vdc | 22,500 / 45,000 W | 112.5 / 225 Arms | 337.5 Apeak |
| AEL-5006-425-56 | 50–425 Vrms / 600 Vdc | 5,600 / 11,200 W | 56 / 112 Arms | 168 Apeak |
| AEL-5008-425-75 | 50–425 Vrms / 600 Vdc | 7,500 / 15,000 W | 75 / 150 Arms | 225 Apeak |
| AEL-5012-425-112.5 | 50–425 Vrms / 600 Vdc | 11,250 / 22,500 W | 112.5 / 225 Arms | 337.5 Apeak |
| AEL-5015-425-112.5 | 50–425 Vrms / 600 Vdc | 15,000 / 30,000 W | 112.5 / 225 Arms | 337.5 Apeak |
| AEL-5019-425-112.5 | 50–425 Vrms / 600 Vdc | 18,750 / 37,500 W | 112.5 / 225 Arms | 337.5 Apeak |
| AEL-5023-425-112.5 | 50–425 Vrms / 600 Vdc | 22,500 / 45,000 W | 112.5 / 225 Arms | 337.5 Apeak |
| AEL-5003-480-18.75 | 50–480 Vrms / 700 Vdc | 2,800 / 5,600 W | 18.75 / 37.5 Arms | 56.25 Apeak |
| AEL-5004-480-28 | 50–480 Vrms / 700 Vdc | 3,750 / 7,500 W | 28 / 56 Arms | 84 Apeak |
Check the operating point: Voltage, RMS current, peak current and power limits apply simultaneously. Full rated voltage and full rated current are therefore available together only when their product does not exceed rated power.
Operating modes and programmable test functions
| Function | Operation | Typical benefit |
|---|---|---|
| CC | Constant load current independent of input voltage | Load and dynamic testing of voltage sources |
| Linear CC | Load current follows the AC input-voltage waveform | Test sine, step, square and PWM voltage sources |
| CR | Current rises in proportion to input voltage | Resistive loading and a softer start for power supplies |
| CV | Load current regulates input voltage to the setpoint | Test current sources, chargers and current-limit characteristics |
| CP | Absorbed power remains constant as voltage changes | Battery discharge and constant-power loading |
| AC rectifier load | Non-linear CC or CC+CR loading | Reproduce rectifier-type loads on UPS systems and PV inverters |
| Store / Recall | Store and recall up to 150 instrument states in EEPROM | Make recurring configurations available without re-entry |
| Auto Sequence | Up to 9 files with up to 32 steps, times and repeats each | Run automated load profiles directly in the instrument |
Frequency, current waveform and measurement
DC to 440 Hz
The 350 and 425 V families operate with DC and 40–440 Hz. The 480 V models are specified for DC and 40–70 Hz.
Crest and power factor
Crest factor is adjustable from 1.414 to 5.0; power factor from 0.1 to 1.0 leading or lagging.
Defined switching angles
Load on and load off are programmable over 0–359°; positive and negative half-wave loading can be selected separately.
Inrush and surge current
Programmable current steps reproduce capacitive inrush current and suddenly connected loads for transient testing.
Capture power-quality quantities
VTHD, ITHD, voltage and current harmonics supplement RMS, peak, maximum and minimum readings.
Measure switching times
Timing functions support UPS transfer-time measurements plus trip and blow times of current-protection components.
Typical applications
UPS systems and inverters
Efficiency, backup and transfer time, on-load start-up, non-linear loading and transient response can be investigated with built-in functions.
PV inverter testing
The load measures efficiency and reproduces resistive plus non-linear loads at the AC output using rectifier and CC+CR operation.
Fuses, circuit breakers and PTCs
Trip and non-trip routines test operation and non-operation using programmable current, time and repetition plus measured trip time.
AC and DC power supplies
CC, CR, CV and CP plus short-circuit, OCP and OPP tests support the characterisation of regulation and protection limits.
Batteries and battery packs
CC and CP discharge with an undervoltage limit or programmed time captures capacity, final voltage and accumulated discharge time.
Production and batch testing
Remote control, stored states, sequences and GO/NG limits support repeatable testing of power supplies and chargers.
Interfaces and automation
| Interface | Availability | Function |
|---|---|---|
| GPIB and RS-232 | Optional combination card or separate cards | Remote control and measurement queries in test systems |
| USB | Optional interface card | Computer connection and remote control |
| LAN | Optional interface card | Network-based remote control |
| Analogue programming input | Optional, 0–10 V | External setpoint input up to full scale for the selected operating mode |
| V monitor / I monitor | Isolated monitor signals scaled to full range, up to ±10 Vpeak | Observe voltage and current waveforms externally |
| Remote sense | Vsense input | Compensate for load-lead voltage drop at the DUT |
| SYNC and master-slave | TTL synchronisation and 15-pin system connection | Synchronise instruments and three-phase load branches |
Parallel operation and three-phase systems
Parallel operation uses identical AEL-5000 models. One master controls up to seven slaves, and the master displays total current and power. Within one single-phase branch, up to eight units and up to 180 kW can be combined. Series connection is not supported.
For three-phase tests, one master synchronises the individual phases in a Δ or Y configuration. Parallel load branches enable documented complete systems up to 540 kW. Available power depends on the number and rated power of identical units on each phase. Test functions are restricted in Boost parallel mode; they are available in 3PH mode.
Installation and infrastructure
| Characteristic | Requirement or configuration |
|---|---|
| Instrument supply | 100–240 Vac ±10%, 47–63 Hz, protective-earth connection required |
| Operating environment | Indoor use, 0–40 °C, 0–85% relative humidity, altitude below 2,000 m |
| Cooling | Front-to-rear airflow; at least 15 cm rear clearance is recommended |
| AEL-5002 / 5003 / 5004 | 177 × 440 × 552.6 mm; 21.5 to 33.5 kg depending on model |
| AEL-5006 / 5008 | 457.8 × 480 × 593 mm; 58 and 70 kg respectively |
| AEL-5012 | 635.7 × 480 × 593 mm; 105 kg |
| AEL-5015 | 813.5 × 480 × 593 mm; 140 kg |
| AEL-5019 / 5023 | 1,283 × 600 × 600 mm; 260 and 295 kg respectively |
Short, twisted load leads reduce inductive voltage spikes and possible control oscillation. With long leads or low voltage, remote sense supports voltage measurement directly at the DUT.
Protection functions
The AEL-5000 monitors input voltage, load current, power dissipation and heat-sink temperature. Following overvoltage, overcurrent, overpower or overtemperature, the load switches off and displays OVP, OCP, OPP or OTP respectively. Fixed OVP, OCP and OPP thresholds are approximately 105% of the relevant model rating; current and power limits can additionally be programmed.
Airflow and rear ventilation openings must remain unobstructed. These instrument protection functions protect the load itself and should be incorporated into the safety concept for the complete test setup.
AEL-5000 FAQ
How do I select the appropriate model?
Check AC or DC voltage, RMS and peak current, and power at the same operating point. Also consider frequency range, Turbo requirements and instrument size.
Is Turbo intended for continuous operation?
No. Turbo is a time-limited doubling of RMS current and power for Fuse, Short, OCP and OPP tests. Permitted duration depends on the test function.
Can different models be connected in parallel?
No. Master-slave parallel operation requires identical models. Up to one master and seven slaves can form a single-phase load branch.
Are GPIB, RS-232, USB and LAN standard?
These computer interfaces are implemented as optional cards. The required interface should therefore be specified when configuring the instrument.
When is remote sense useful?
Remote sense compensates for voltage drop across longer load leads and is particularly useful at low voltage and high current. Sense-lead polarity must be observed.
Can the AEL-5000 test UPS systems and inverters?
Yes. Built-in routines support efficiency, backup and transfer-time testing; load angles, half-wave loading, inrush current and non-linear loads extend the investigation.
Is the series suitable for PV inverter testing?
Yes. Efficiency can be measured at the AC output, while rectifier or CC+CR operation reproduces resistive plus non-linear loads.
Can fuses and circuit breakers be tested?
Yes. Trip and non-trip tests use adjustable current, time and repetition. Turbo temporarily extends available RMS current and power for these tests.
Technical consultation and project enquiry
To select an appropriate AEL-5000 configuration, provide the AC and DC voltage range, required RMS and peak current, continuous and short-term power, and the intended current waveforms and test functions. Include frequency, interface, number of phases, and requirements for parallel operation, wiring and cooling.